FIRE EXTINGUISHER

We provide services, supply, delivery and install for fire extinguisher including commonly used by regulation of Bomba is 9kg ABC Dry Powder and 2kg CO2 Fire Extinguisher.





FIRE ALARM SYSTEM


FIRE ALARM SYSTEM TYPE:
1) CONVENTIONAL
- direct wiring from point
2) SEMI ADDRESSABLE
- direct wiring from point to sub panel (rppu)
3) ADDRESSABLE
- looping cabling

The devices for fire alarm system can be divided into: -
- Main Fire alarm panel c/w mimic
- Fire detection and alarm devices Installation
- Break-glass installation

Fire alarm panel c/w mimic diagram
The fire alarm panel consists of one main panel, which is situated in the FIRE control room. The exact location is situated in shop drawing. The main fire alarm panel is consists of a main panel and a LED drives mimic.
The installation begins with the fabrication of the main panel console. Upon completion of the console, it is move to the fire control room.

Upon securing of the main fire console, main panel is installed and secured by screw. Termination of loop cables and power cable is then done. Prior to the termination, checking is done to confirm there no earth fault on cable.
The termination of cable is conducted by manufacturer certified engineer and technician. Upon termination of cable and all cables are confirmed no fault, testing and commissioning software is used to download and detect present of remote field devices such as detectors.

Fire detector installation
The fire detector used is optical type (Smoke detector). Typically detectors are installed at the topmost level i.e. below the slab or below false ceiling.
This project utilizes concealed conduit in slab. The detectors installed right under the 2 way or end box.

Material Proposed

·        Fire Alarm System Control Panel
·        heat detector
·        smoke detector
·        break glass
·        Alarm bell

Here some photos from our past project :










WET RISER SYSTEM


INSTALLATION PROCEDURE

Requirement for wet riser system
The wet riser system is required for building where the topmost floor is higher than 30.5 meter above the fire appliances access level. Wet riser comprises of duty pump and standby pump set which discharging water into a 150 mm pipe, A jockey pump is used to maintain pressure in the system. The water supply pipe 150 mm diameter.

Requirement for breeching inlet installation
4-way breeching inlet should be located not more than 30 meters from the nearest external hydrant outlet and not more than 1B meter from fire appliances access.

Requirement for landing valve installation
Landing valves are provided on each floor and should comply to M.S.1489: Part 1. Landing valves are located within fire access lobbies, protected staircase or other protected lobbies. It is installed not more than 750 mm above ground level. Any boxes that are to be installed for landing valves must comply with M.S.1489: Part 1.
 Fire hose of rubber lined type complete with 65 mm diameter quick coupling and nozzle be provided in a hose cradle besides each landing valve.

Here some photos for our project reference: 

3 WAY OBLOQUE LANDING VALVE

3 WAY LANDING VALVE AT THE TOP OF BUILDING

PUMP INSTALLATION OF WET RISER SYSTEM

INSTALLATION OF BREECHING INLET ALLIGNMENT

COMPLETE SET OF LANDING VALVE/ HOSE/ CRADDLE IN RISER ROOM

DRY RISER COMPLETE SET

BREECHING INLET INSTLLATION C/W EXTENDED PIPE

2 BREECHING INLET C/W CABINET

3 WAY LANDING VALVE TESTING




HOSE REEL SYSTEM


Installation Procedure

The hose reels are usually placed such that all areas are within 30 meters hose coverage of each hose reel. One hose reel should be provided for every 800 meter square of usable floor space. Hose reel are usually located in prominent position at each floor level along escape routes or beside exit doors or staircase. Each hose reel outlet is to discharge a minimum of 30 l/ min of water within 6 meters of all parts of the space protected.

Material Proposed

·        Hose Reel Drum
·        Hose Reel Hose
·        Hose Reel nozzle
·        Hose Reel clip
·        Isolation gate valve (ะค25mm)


Here some photos for our Hose Reel Drum Installation

Delivery of Hose Reel Drum

Sample from our installation of Hose Reel Drum set

Complete set for Hose Reel Drum instllation at appartment corridor

Hose Reel drum installation at Carpark



CO2 SYSTEM (GAS SUPPRESSION SYSTEM)


AUTOMATIC CARBON DIOXIDE EXTINGUISHING SYSTEM


DESCRIPTION
Carbon Dioxide Extinguishing System consists of carbon dioxide cylinders, steel piping, discharge nozzles, heat detector, smoke detector and a control panel, which monitors the space, activates both visual and audio alarms before releasing the gas.

The carbon dioxide is discharged after a time delay upon detection of fire to warn any occupant to evacuate the room. Such system is usually provided for electrical transformer rooms, switches rooms and standby generator rooms and should not be installed for rooms, which are normally occupied.

Design Standards
The relevant clause in the Uniform Building By-Laws 1984, relating to carbon dioxide extinguishing systems is By Law 235 and applicable standard is:
 -         NFPA 12


Material Proposed
·        45Kg CO2 Cylinder
·        Sch 40 Pipe
·        Fire Curtain
·        24 V DC Tripping device
·        CO2 System Control Panel
·        Conventional Heat Detector
·        Conventional Smoke Detector
·        24 V DC Alarm Bell
·        SLA Batteries
·        Key Switch

Here some photos from our project reference. Have a look ! :
CO2 PANEL FOR LV SWITCH ROOM

TERMINATION AND T&C BY OUR EXPERT FOREMAN

NORMAL CONDITION CO2 PANEL 

SERVICING PILOT CYLINDER

SERVICING CONNECTION HOSE 45KG CO2 CYLINDER
45KG CO2 CYLINDER C/W PILOT CYLINDER


Here some info for our reference based from consultant design of electrical rooms.
CO2 PANEL WIRING DIAGRAM

CO2 PIPING DESIGN

LAYOUT ELECTRICAL ROOM BASED FROM CONSULTANT DESIGN