FIRE ALARM SYSTEM
FIRE ALARM SYSTEM TYPE:
1) CONVENTIONAL
- direct wiring from point
2) SEMI ADDRESSABLE
- direct wiring from point to sub panel (rppu)
3) ADDRESSABLE
- looping cabling
The
devices for fire alarm system can be divided into: -
- Main Fire alarm
panel c/w mimic
- Fire detection and
alarm devices Installation
- Break-glass
installation
Fire alarm panel c/w mimic diagram
The
fire alarm panel consists of one main panel, which is situated in the FIRE
control room. The exact location is situated in shop drawing. The main fire
alarm panel is consists of a main panel and a LED drives mimic.
The
installation begins with the fabrication of the main panel console. Upon
completion of the console, it is move to the fire control room.
Upon
securing of the main fire console, main panel is installed and secured by
screw. Termination of loop cables and power cable is then done. Prior to the
termination, checking is done to confirm there no earth fault on cable.
The
termination of cable is conducted by manufacturer certified engineer and
technician. Upon termination of cable and all cables are confirmed no fault,
testing and commissioning software is used to download and detect present of
remote field devices such as detectors.
Fire detector installation
The
fire detector used is optical type (Smoke detector). Typically detectors are
installed at the topmost level i.e. below the slab or below false ceiling.
This
project utilizes concealed conduit in slab. The detectors installed right under
the 2 way or end box.
Material Proposed
·
Fire Alarm System Control Panel
·
heat detector
·
smoke detector
·
break glass
·
Alarm bell
Here some photos from our past project :
WET RISER SYSTEM
INSTALLATION PROCEDURE
Requirement
for wet riser system
The
wet riser system is required for building where the topmost floor is higher
than 30.5 meter above the fire appliances access level. Wet riser comprises of
duty pump and standby pump set which discharging water into a 150 mm pipe, A
jockey pump is used to maintain pressure in the system. The water supply pipe 150
mm diameter.
Requirement
for breeching inlet installation
4-way
breeching inlet should be located not more than 30 meters from the nearest
external hydrant outlet and not more than 1B meter from fire appliances access.
Requirement
for landing valve installation
Landing
valves are provided on each floor and should comply to M.S.1489: Part 1.
Landing valves are located within fire access lobbies, protected staircase or
other protected lobbies. It is installed not more than 750 mm above ground
level. Any boxes that are to be installed for landing valves must comply with
M.S.1489: Part 1.
Here some photos for our project reference:
3 WAY OBLOQUE LANDING VALVE
3 WAY LANDING VALVE AT THE TOP OF BUILDING
PUMP INSTALLATION OF WET RISER SYSTEM
INSTALLATION OF BREECHING INLET ALLIGNMENT
COMPLETE SET OF LANDING VALVE/ HOSE/ CRADDLE IN RISER ROOM
DRY RISER COMPLETE SET
BREECHING INLET INSTLLATION C/W EXTENDED PIPE
2 BREECHING INLET C/W CABINET
3 WAY LANDING VALVE TESTING
HOSE REEL SYSTEM
Installation Procedure
The
hose reels are usually placed such that all areas are within 30 meters hose
coverage of each hose reel. One hose reel should be provided for every 800
meter square of usable floor space. Hose reel are usually located in prominent
position at each floor level along escape routes or beside exit doors or staircase.
Each hose reel outlet is to discharge a minimum of 30 l/ min of water within 6
meters of all parts of the space protected.
Material Proposed
·
Hose Reel Drum
·
Hose Reel Hose
·
Hose Reel nozzle
·
Hose Reel clip
·
Isolation gate valve (ะค25mm)
Here some photos for our Hose Reel Drum Installation
Delivery of Hose Reel Drum
Sample from our installation of Hose Reel Drum set
Complete set for Hose Reel Drum instllation at appartment corridor
Hose Reel drum installation at Carpark
CO2 SYSTEM (GAS SUPPRESSION SYSTEM)
AUTOMATIC
CARBON DIOXIDE EXTINGUISHING SYSTEM
DESCRIPTION
Carbon
Dioxide Extinguishing System consists of carbon dioxide cylinders, steel
piping, discharge nozzles, heat detector, smoke detector and a control panel,
which monitors the space, activates both visual and audio alarms before
releasing the gas.
The carbon
dioxide is discharged after a time delay upon detection of fire to warn any
occupant to evacuate the room. Such system is usually provided for electrical
transformer rooms, switches rooms and standby generator rooms and should not be
installed for rooms, which are normally occupied.
Design
Standards
The
relevant clause in the Uniform Building By-Laws 1984, relating to carbon
dioxide extinguishing systems is By Law 235 and applicable standard is:
-
NFPA 12
Material Proposed
·
45Kg CO2 Cylinder
·
Sch 40 Pipe
·
Fire Curtain
·
24 V DC Tripping device
·
CO2 System Control Panel
·
Conventional Heat Detector
·
Conventional Smoke Detector
·
24 V DC Alarm Bell
·
SLA Batteries
·
Key Switch
Here some photos from our project reference. Have a look ! :
CO2 PANEL FOR LV SWITCH ROOM
TERMINATION AND T&C BY OUR EXPERT FOREMAN
NORMAL CONDITION CO2 PANEL
SERVICING PILOT CYLINDER
SERVICING CONNECTION HOSE 45KG CO2 CYLINDER
45KG CO2 CYLINDER C/W PILOT CYLINDER
Here some info for our reference based from consultant design of electrical rooms.
CO2 PANEL WIRING DIAGRAM
CO2 PIPING DESIGN
LAYOUT ELECTRICAL ROOM BASED FROM CONSULTANT DESIGN